4-30
FM 453 Servo Drive / Step Drive Positioning Module
C79000-G7076-C453-01
A 3.5 mm (0.13 inches) screwdriver or power screwdriver.
To wire the front connector (with screw-type terminals):
1. Remove the cover from the front connector.
2. Strip the insulation from the lines (8 to 10 mm).
3. Are you using ferrules?
If so: Strip the insulation from the wires over 10mm. Press the ferrules
onto the lines.
4. Apply the supplied cable grip to the connector.
5. Start wiring up from the bottom, otherwise from the top. Screw down un-
used terminals as well.
The tightening torque should be 0.6-0.8 Nm.
6. Tighten the cable grip on the cable strand.
7. Close the front connector.
8. Label the connections on the supplied label.
9. Plug front connector onto the module.
For further details on wiring up a front connector, please refer to the manual
S7-400/M7-400, Programmable Controller, Hardware and Installation.
When using shielded cables, the following additional steps are necessary:
1. The cable shielding must be connected to a grounded shielding bus over a
large contact area in the proximity of the FM 453.
Please refer to the manual S7-400/M7-400 Programmable Controller,
Hardware and Installation.
2. Connect the shielded line to the module, but do not connect the shielding
there.
Tools Required
Procedure for Wir-
ing the Front Con-
nector
Shielded Cables
Wiring the FM 453
Summary of Contents for SIMATIC FM 453