Parameter:
Demand Data Log > Demand Window Type
•
Default Setting:
Fixed
This selects how the
Demand Window
is defined:
–
Fixed
: the maximum, minimum and mean values demand statistics are calculated over a fixed
window duration. At the end of each window the internal statistics are reset and a new window is
started. The first window is started when the setting is entered.
–
Peak
: Records the maximum and minimum values since the
Demand Data Log
feature was last
reset.
–
Rolling
: the maximum, minimum and mean values demand statistics are calculated over a
moving window duration. The internal statistics are updated when the window advances. The oldest
stored values when new samples are recorded at the end of the
Demand Window
.
Maximum and minimum values (and times) are stored for previous data log periods.
Parameter:
Demand Data Log > Demand Reset
•
Default Setting:
<None>
Demand data log statistics can be reset from the device fascia.
The statistics can also be reset from a binary input or communication command. After reset the update
period and window are immediately restarted.
Configuration > Data Storage > Demand Data Log
Parameter
Range
Default Setting
Data log period
5 to 10 min, Δ 1 min
10 to 60 min, Δ 5 min
5 min
Clear data log
Demand window
1 to 24 hr, Δ 1 hr
24 hr
Demand window type
Fixed, peak, rolling
Fixed
Demand reset
The demand measurement function corresponds to the following logical nodes in IEC 61850:
Table 3-3
Demand Measurements
7SR5110 (Current
only)
Ia (Ia =)
MEAS
MeanIMMXU1
A.phsA
Ib (Ib =)
MEAS
MeanIMMXU1
A.phsB
Ic (Ic =)
MEAS
MeanIMMXU1
A.phsC
Ineut (Ig =)
MEAS
MeanIMMXU1
A.neut
Ia (Ia =)
MEAS
MinIMMXU1
A.phsA
Ib (Ib =)
MEAS
MinIMMXU1
A.phsB
Ic (Ic =)
MEAS
MinIMMXU1
A.phsC
Ineut (Ig =)
MEAS
MinIMMXU1
A.neut
Ia (Ia =)
MEAS
MaxIMMXU1
A.phsA
Ib (Ib =)
MEAS
MaxIMMXU1
A.phsB
Ic (Ic =)
MEAS
MaxIMMXU1
A.phsC
Ineut (Ig =)
MEAS
MaxIMMXU1
A.neut
Device Functionality
3.6 Data Storage
Reyrolle 7SR5, Transformer Protection Device, Device Manual
95
C53000-G7040-C015-1, Edition 11.2019