Functions > Protection > 67 > Gn 67G
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Char Angle
-95° to +95°, Δ 1°
-15°
Minimum Voltage
0.33 V to 67 V, Δ 0.5 V
0.33 V
Functions > Protection > 67 > Gn 67GS
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Char Angle
-95° to +95°, Δ 1°
-15°
Minimum Voltage
0.33 V to 67 V, Δ 0.5 V
0.33 V
Compensated Network
Enabled
Disabled
Disabled
Wattmetric
Enabled
Disabled
Disabled
Wattmetric Power
0.05 to 20 ⋅ I
rated
⋅ W, Δ 0.05
⋅ I
rated
⋅ W
0.1 ⋅
I
rated
⋅ W
Ires Select
Ires
Ires Real
Ires
Functions > Protection > 67 > Gn 67N
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Polarizing Quantity
NPS
ZPS
ZPS
Char Angle
-95° to +95°, Δ 1°
-15°
Minimum Voltage
0.33 V to 3 V, Δ 0.5 V
0.33 V
Information List
Input/Output Matrix
General Pickup User Logic
Type
67 FWD PhA
Output
67 REV PhA
Output
67 FWD PhB
Output
67 REV PhB
Output
67 FWD PhC
Output
67 REV PhC
Output
67G FWD
Output
67G REV
Output
Inhibit Wattmetric
Input
67GS FWD
Output
67GS REV
Output
Wattmetric Po> Operated
Output
67N FWD
Output
67N REV
Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.19.6
Protection and Automation Functions
5.19 67 Directional Overcurrent/Earth Fault
Reyrolle 7SR5, Transformer Protection Device, Device Manual
287
C53000-G7040-C015-1, Edition 11.2019