Table 7-1
Points List
User Logic
IEC 60870-5-1 03
DNP3
Modbus
User mimic status 1 (to
10)
N
N
N
User SP serial command 1
(to 8) (On/Close)
Y
Y
Y
User DP serial command 1
(to 8) (On/Close)
Y
Y
Y
User DP serial command 1
(to 8) (Off/Open)
Y
Y
Y
The operating mode of the controllable in IEC 61850s can be selected with the appropriate control model.
3 different control model types are available:
•
Direct without feedback monitoring (direct w. normal secur)
•
Direct with feedback monitoring (direct w. enh. security)
•
With SBO with feedback monitoring (SBO w. enh. security)
i
i
NOTE
SBO without feedback monitoring is not supported.
The
Control Confirmation ID
, when active, must be entered to proceed with the control action. If any
logic interlocking has been created within the Reylogic the item may not change state and the operation
blocked.
Control from Control Mode Menu/Fascia Function Keys
The device provides a number of preconfigured control items from the fascia menus. From the
Home Screen
the
Down
arrow can be pressed to access the
Main Menu
. The user can then, using the arrows, scroll to the
Control Mode
menu. The
Right
arrow is used to enter the
Control Mode
menu.
[sc_7SR5_ControlModeMenu, 1, --_--]
Figure 7-1
Control Mode Menu
The following items are available as preconfigured controllable items located in the
Control Mode
menu:
•
CB Open/Close
•
EF In/Out
Control Functions
7.1 Device Control Functions