Information
A59VxPTOV*.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
A59VxPTOV*.Op
Information
Element Operated
0
1
A59VxPTOV*.Op.general
0
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
TRUE: 1
FALSE: 0
A59VxPTOV*.Str
Information
Element picked up
0
1
A59VxPTOV*.Str.general
0
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
TRUE: 1
FALSE: 0
Information List
Input/Output Matrix
General
Pickup
User Logic
Type
IEC
60870-5-1
03
DNP3
MODBUS
RTU
Inhibit 59Vx-n
Inhibit 59Vx-n
Input
59Vx-n
59Vx-n Operated
Output
Y
Y
Y
59Vx-n
Pickup
59Vx-n Pickup
Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.18.7
Protection and Automation Functions
5.18 59Vx Overvoltage Protection – Vx
274
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019