Element
Setting Values
81-3
81-3 Hysteresis
0.1 %
81-3
81-3 Delay
5 s
81-3
81-3 Input Selection
VT1/2/3
81-4
81-4 Element
Enabled
81-4
81-4 Operation
Under
81-4
81-4 Setting
49 Hz
81-4
81-4 Hysteresis
0.1 %
81-4
81-4 Delay
5 s
81-4
81-4 Input Selection
VT1/2/3
Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
81 Frequency
Enabled
Disabled
Disabled
Functions > Protection > 81 > Gn 81-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Input Selection
VT1/2/3
VT4
VT1/2/3
Operation
Under
Over
Under
Setting
40 to 70 Hz, Δ 0.01 Hz
49.5 Hz
Hysteresis
0 to 2 %, Δ 0.1 %
0.1 %
Delay (DTL)
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
1 s
IEC 61850 Functional Information Mapping
A81PTUF*.Mod
Information
81 Frequency Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A81PTUF*.Mod.stVal
5
5
2
1
5.20.5
5.20.6
Protection and Automation Functions
5.20 81 Frequency Protection – "f>" or "f<"
292
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019