Functions > Protection > 37 > Gn 37-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Pickup Option
Any
All
All
IEC 61850 Functional Information Mapping
A37PTUC*.Mod
Information
37 Undercurrent Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A37PTUC*.Mod
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A37PTUC*.Health
Information
Device Healthy
0
1
A37PTUC*.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
A37PTUC*.Op
Information
Element Operated
0
1
A37PTUC*.Op.general
0
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
TRUE: 1
FALSE: 0
5.5.6
Protection and Automation Functions
5.5 37 Undercurrent Protection – Phase
174
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019