Communication
COM1 Traffic
Activity on the rear RS485 port
Tx1
Transmitted Data
Rx1
Received Data
Ethernet Information
Version
Firmware Version of EN100
Part#
Ethernet Meter 1
Network Config
Ethernet Meter 2
MAC Address: EN100 Mac Address
Ethernet Meter 3
IP Address: IPAddress
Ethernet Meter 4
NM Address: Subnet Mask Address
Ethernet Meter 5
GW Address: Gateway Address
Ethernet Meter 6
3 Functions
NT1 Address
NTP Server Address. The contents of this
line toggle in intervals of approx. 10 s
between the server address and the time
elapsed since the last synchronization.
If the server address is displayed the star
(
*
) symbolizes an active SNTP server. The
time is displayed for up to 999 s (i.e.
approx. 16 min). A display of 999 right
after startup of the device signals that
there is no synchronization via SNTP.
This line also signals the existence of
corrupt parameters. This is the case when
the parameter settings of the module do
not match the parameter settings of the
device.
The third function deals with the signaliza-
tion of a double IP address. When a device
starts up in the network, the existence of
the IP address is checked. If the address
already exists in the network, a static infor-
mation to that effect is displayed in line 6:
6 !!MAC!!0007E908FCC8
In that case, the device will not be
connected to the network. The double IP
address can be identified from the MAC
address displayed. which is part of the
existing IP address.
Ethernet
Meter 7
Chan 1/2 = Up/Up
Shows that both channels are active. This
information is only displayed if the internal
switch is active. If 1 of the 2 channels is
down, the ring is broken.
Ethernet
Meter 8
Rx/TxCnt=
Shows the number of telegrams received
and transmitted. This counter is not reset
and signals that the interface is working
correctly.
Ethernet
Meter 9
Rx/TxErr=
The telegram errors found are counted.
Ethernet
Meter 10
Rx/Tx10s=
Instruments and Meters
8.2 Instruments
398
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019