Functions > Protection > 46 > 46IT-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Char
DTL
IEC-NI, IEC-VI
IEC-EI, IEC-LTI
ANSI-EI, ANSI-MI
ANSI-VI
IEC-NI
TMS (IEC/ANSI)
0.025 to 1.6, Δ 0.01
1.6 to 5, Δ 0.1
5 to 100, Δ 1
1
Delay (DTL)
0 to 20 s Δ 0.01 s
5 s
Reset
IEC/ANSI Decaying
0 to 60 s Δ 1 s
0 s
IEC 61850 Functional Information Mapping
A46DTPTOC*.Mod
Information
46 NPS Overcurrent Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A46DTPTOC*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A46DTPTOC*.Health
Information
Device Healthy
0
1
A46DTPTOC*.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
5.7.6
Protection and Automation Functions
5.7 46 Negative-Sequence Overcurrent Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual
185
C53000-G7040-C015-1, Edition 11.2019