Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
81HB2 2nd Harmonic
Enabled
Disabled
Disabled
Functions > Protection > 81HB2 > Gn 81HB2-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
0.1 to 0.5 ⋅ I, Δ 0.01 ⋅ I
0.2 ⋅ I
Bias
Cross
Phase
Sum
Cross
IEC 61850 Functional Information Mapping
A81HB2PHAR*.Mod
Information
81HB2 2nd Harmonic Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A81HB2PHAR*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A81HB2PHAR*.Health
Information
Device Healthy
0
1
A81HB2PHAR*.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
6.6.5
6.6.6
Supervision Functions
6.6 81HB2 Inrush Current Detection
Reyrolle 7SR5, Transformer Protection Device, Device Manual
367
C53000-G7040-C015-1, Edition 11.2019