Functions > Protection > 87T > Gn 87T Common
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
W3 ICT Connection
See
11
Yy0
87T Zone Inputs
W1, W2, W3
11
<all>
87T HB Select
Operate
Line
Operate
Functions > Protection > 87T > 87T-BD-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
HB2 Element
Enabled
Disabled
Disabled
HB2 Bias
Cross
Phase
Sum
Cross
HB2 Setting
0.1 to 0.5 p.u, Δ 0.01 p.u
0.15x
HB5 Element
Enabled
Disabled
Disabled
HB5 Bias
Cross
Phase
Sum
Cross
HB5 Setting
0.1 to 0.5 p.u, Δ 0.01 p.u
0.3x
Gn Element
Enabled
Disabled
Disabled
Gn Setting
0.1 to 2 p.u, Δ 0.05 p.u
0.2 ⋅
I
rated
Gn S1
0.1 to 0.7x, Δ 0.05 p.u
0.2x
Gn S1L
1 to 20 p.u, Δ 0.5 p.u
4 ⋅ I
rated
Gn S2 Type
Line
Curve
Line
Gn S2
1 to 2x, Δ 0.1x
1.5x
Gn Delay
0 to 1 s, Δ 5 ms
0 s
External Fault
1 ⋅ I
rated
to 10 ⋅ I
rated
, Δ 0.05 ⋅
I
rated
2.4 ⋅
I
rated
Clearance Time
0 s to 1000 s, Δ
0.3 s
Functions > Protection > 87T > 87T-HS-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
1 to 30 ⋅ I
rated
, Δ 1 ⋅ I
rated
20 ⋅ I
rated
Gn Delay
0 to 1 s, Δ 5 ms
0 s
Protection and Automation Functions
5.22 87T Transformer Differential Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual
331
C53000-G7040-C015-1, Edition 11.2019