Application and Setting Notes
Parameter:
Element
•
Default setting:
Disabled
This setting is used to allow the element to be switched on and off if it is not required. A separate setting
is provided for each element. This setting can be used to select the number of elements required.
Parameter Value
Description
Disabled
This element is switched out and is not available.
Enabled
The element is available for use and can be parame-
terized.
Parameter:
Dir. Control
•
Default setting:
Non-Dir
This setting is used to define whether the element will operate for earth faults detected in the
Forward
or
Reverse
direction based on the 67N directional element decision or for any earth fault regardless of
the 67N direction. This allows the earth fault protection to have different current and time settings for
forward, reverse and non-directional faults by using three 67N function elements.
This parameter is not provided in devices that do not have voltage inputs or for current inputs that are
not polarized by the voltage inputs.
Parameter Value
Description
Non-Dir
Select this setting if the element is to operate regard-
less of the current direction or presence of voltage.
Forward
Select this setting if the element is to operate only in
a forward direction.
Reverse
Select this setting if the element is to operate only in
a reverse direction.
Parameter:
Setting
•
Default setting: 0.5 x I
n
(0.5 ⋅ I
rated
)
This setting defines the operating current threshold of the element. The operation timing will then be
dependent on the selected delay setting.
This setting should be set to suit the individual application.
Parameter:
Delay
•
Default setting:
0 s
This time delay setting should be set to suit the individual application.
Parameter:
VTS Action
•
Default setting:
Off
Voltage transformer failure can affect the directional decision and introduce an error. This setting selects
if operation of the
60VTS Voltage Transformer Supervision
element automatically affects the
operation of the element.
5.13.4
Protection and Automation Functions
5.13 50N Instantaneous Earth Fault – Calculated
Reyrolle 7SR5, Transformer Protection Device, Device Manual
223
C53000-G7040-C015-1, Edition 11.2019