IEC 61850 Functional Information Mapping
Functional Description
Logical Device LD
Logical Node LN
Instantiated Data Object
DOI
47-(Gn)
PROT
A47PTOV(Gn)
Mod
Beh
Health
NamPlt
Str
Op
A47PTOV*.Mod
Information
47 Sequence Voltage Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A47PTOV*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A47PTOV*.Health
Information
Device Healthy
0
1
A47PTOV*.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
A47PTOV*.Op
Information
Element Operated
0
1
A47PTOV*.Op.general
0
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
TRUE: 1
FALSE: 0
5.9.6
Protection and Automation Functions
5.9 47 Sequence Overvoltage Protection
Reyrolle 7SR5, Transformer Protection Device, Device Manual
197
C53000-G7040-C015-1, Edition 11.2019