Settings Menu
Configuration > Function config
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
CB Counters
Enabled
Disabled
Disabled
I
2
t CB Wear
Enabled
Disabled
Disabled
Functions > Control > 52 > CB-n
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
Close CB Pulse
2 s
Reclaim Timer
2 s
Minimum LO Delay
2 s
Reset LO by Timer
Enabled
Disabled
Enabled
Close Delay
10 s
Blocked Close Delay
5 s
Controls Latched
Latch
Travel Alarm
1 s
Open Delay
10 s
Open Pulse
1 s
DBI Alarm
0 s
Trip Time Alarm
0.2 s
Trip Time Adjust
0.015 s
Functions > Control > 52 > CB-n Counters
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
Total Trip Count
Enabled
Disabled
Disabled
Total Trip Count Target
100
Delta Trip Count
Enabled
Disabled
Disabled
Delta Trip Count Target
CB Frequent Ops Count
Enabled
Disabled
Disabled
CB Freq Ops Count Target
CB Count to 79 Block Man
Open
Enabled
Disabled
Disabled
CB Count to 79 Block
Enabled
Disabled
Disabled
CB Count to 79 Block Target
7.2.5
Control Functions
7.2 52 Circuit-Breaker Control
Reyrolle 7SR5, Transformer Protection Device, Device Manual
387
C53000-G7040-C015-1, Edition 11.2019