81HB2 Inrush Current Detection
Overview of Functions
The elements can be used to block operation of selected functions where these are liable to mal-operate
during transformer switch in conditions.
Structure of the Function
The inrush detector function has group dependent settings. These settings can be different in each set-tings
group – group numbers (Gn) 1 to 4.
This function corresponds to the logical nodes
A81HB2PHAR*
in IEC 61850.
The function monitors the primary system using the 3 phase current inputs e.g. CT1/2/3.
The inrush detector function (81HB2) is summarized below:
•
High speed (instantaneous) operate characteristic
•
Logic outputs are provided to block selected device functionality and for external indications
Logic of the Function
[lo_7SR5_81HB2logicdiagram, 1, en_US]
Figure 6-15
Logic Diagram: 81HB2 Inrush Current Detection
Application and Setting Notes
Parameter:
81HB2 Element
•
Default setting:
Disabled
This setting is used to allow the element to be switched on and off if it is not required. A separate setting
is provided for each element. These setting can be used to select the number of elements required.