Functions > Protection > 51 > Gn 51-n
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
Dir. Control
8
Non-Dir
Forward
Reverse
Non-Dir
Setting
0.05 to 2.5 ⋅ I
rated
, Δ 0.01
I
rated
1 ⋅ I
rated
Char
DTL
IEC-NI
IEC-VI
IEC-EI
IEC-LTI
ANSI-EI
ANSI-MI
ANSI-VI
IEC-NI
Time Mult (IEC/ANSI)
0.01 to 1.6, Δ 0.01
1.6 to 5, Δ 0.1
5 to 100, Δ 1
1
Delay (DTL)
0 to 20 s Δ 0.01 s
5 s
Min Operate Time
0 to 20 s Δ 0.01 s
0 s
Follower DTL
0 to 20 s Δ 0.01 s
0 s
Reset
IEC/ANSI Decaying
0 to 60 s Δ 1 s
0 s
VTS Action
8
Off
Inhibit
Non-Dir
Off
81HB2 Inhibit
No
Yes
No
79 Delayed Inhibit
No
Yes
No
21LB-3P Inhibit
8
No
Yes
No
21LB-1P Inhibit
8
No
Yes
No
51V Multiplier
8
0.25 to 1 Δ 0.05
0.5
Functions > Protection > 51 > Gn 51CL-n
Parameter
Setting Options
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
0.05 to 2.5 ⋅ I
rated
, Δ 0.01
I
rated
1 ⋅ I
rated
8
Applies only to devices with VT inputs.
Protection and Automation Functions
5.14 51 Time-Delayed Overcurrent – Phase
Reyrolle 7SR5, Transformer Protection Device, Device Manual
241
C53000-G7040-C015-1, Edition 11.2019