Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
MMTR*.DmdVArh
Information
Value
Reactive Energy Imp MMTR*.DmdVArh.actVal
Measured Value
Value
MMTR*.DmdVArh.units.SIUnit
73
VArh
MMTR*.DmdVArh.units.multiplier
3
None
MMTR*.DmdVArh.pulsQty
10
3
None
MMTR*.DmdWh
Information
Value
Active Energy Imp
MMTR*.DmdWh.actVal
Measured Value
Value
MMTR*.DmdWh.units.SIUnit
72
Wh
MMTR*.DmdWh.units.multiplier
3
None
MMTR*.DmdWh.pulsQty
10
4
None
MMTR*.SupVArh
Information
Value
Reactive Energy Exp MMTR*.SupVArh.actVal
Measured Value
Value
MMTR*.SupVArh.units.SIUnit
72
VArh
MMTR*.SupVArh.units.multiplier
3
None
MMTR*.SupVArh.pulsQty
10
5
None
MMTR*.SupWh
Information
Value
Active Energy Imp
MMTR*.SupWh.actVal
Measured Value
Value
MMTR*.SupWh.units.SIUnit
72
Wh
MMTR*.SupWh.units.multiplier
3
None
MMTR*.SupWh.pulsQty
10
6
None
3
Dependant on the Reactive Imp Energy Unit setting. The unit of energy is calculated by combining the multiplier and the pulsQty.
By default this is 10
3
⋅ 10 = 10,000 or 10 kVArh.
4
Dependant on the Active Imp Energy Unit setting. The unit of energy is calculated by combining the multiplier and the pulsQty. By
default this is 10
3
⋅ 10 = 10,000 or 10 kVArh.
5
Dependant on the Reactive Exp Energy Unit setting. The unit of energy is calculated by combining the multiplier and the pulsQty.
By default this is 10
3
⋅ 10 = 10,000 or 10 kVArh.
6
Dependant on the Active Exp Energy Unit setting. The unit of energy is calculated by combining the multiplier and the pulsQty. By
default this is 10
3
⋅ 10 = 10,000 or 10 kVArh.
Device Functionality
3.6 Data Storage
Reyrolle 7SR5, Transformer Protection Device, Device Manual
111
C53000-G7040-C015-1, Edition 11.2019