
Parameter:
Delay
•
Default setting:
0.1 s
This is the time delay setting for the DTL element. This should be set to suit the individual application.
Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
59Vx Overvoltage
Enabled
Disabled
Disabled
Functions > Protection > 59Vx > Gn 59Vx-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
5 to 200 V, Δ 0.5 V
80 V
Hysteresis
0 to 80 %, Δ 0.1 %
3 %
Delay
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0.1 s
IEC 61850 Functional Information Mapping
A59VxPTOV*.Mod
Information
59Vx Overvoltage Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A59VxPTOV*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A59VxPTOV*.Health
Information
Device Healthy
0
1
5.18.5
5.18.6
Protection and Automation Functions
5.18 59Vx Overvoltage Protection – Vx
Reyrolle 7SR5, Transformer Protection Device, Device Manual
273
C53000-G7040-C015-1, Edition 11.2019