Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
50BF CB Fail
Enabled
Disabled
Disabled
Functions > Protection > 50BF > Gn 50BF-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
0.05 to 2 ⋅ I
rated
, Δ 0.05 I
rated
0.2 ⋅
I
rated
I4 Setting
0.05 to 2 ⋅ I
rated
, Δ 0.05 I
rated
0.05 ⋅
I
rated
Delay 1
0.02 to 60 s, Δ 0.005 s
60 ms
Delay 2
0.02 to 60 s, Δ 0.005 s
120 ms
CB Fail outputs will be issued providing any of the 3 phase currents are above the setting or the current in the
fourth CT is above
I4
setting for longer than the
50BF-n Delay
setting, or for a mechanical protection trip
the circuit-breaker is still closed when the
50BF-n Delay
setting has expired, indicating that the fault has
not been cleared.
If the
50BF CB Faulty
input
Input Config > Input Matrix > 50BF CB Faulty
is energized when
a CB trip is given then
Delay 1
and
Delay 2
will be by-passed and the output given immediately.
IEC 61850 Functional Information Mapping
A50BFRBRF*.Mod
Information
50BF CB Fail Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A50BFRBRF*.Mod.stVal
5
5
2
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A50BFRBRF*.Health
Information
Device Healthy
0
1
6.1.5
6.1.6
Supervision Functions
6.1 50BF Circuit-Breaker Failure Protection – 3 Pole
Reyrolle 7SR5, Transformer Protection Device, Device Manual
343
C53000-G7040-C015-1, Edition 11.2019