[dw_7SR5_function87GHApplicationAndSettingNotes4, 1, en_US]
Figure 5-47
REF Relay Circuit
Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
87GH Restricted EF
Enabled
Disabled
Disabled
Functions > Protection > 87 > Gn 87GH-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
0.02 to 0.95, Δ 0.005 I
rated
0.2 I
rated
Delay (DTL)
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0 s
IEC 61850 Functional Information Mapping
A87GHPTOC*.Mod
Information
87GH Restricted EF Enabled (Function Config)
x
0
1
1
Element Disabled
1
x
0
0
Element Inhibited
x
x
1
0
A87GHPTOC*.Mod.stVal
5
5
2
1
5.21.5
5.21.6
Protection and Automation Functions
5.21 87GH Restricted Earth-Fault Protection – High-Impedance
304
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019