A51GPTOC*.Op
Information
Element Operated
0
1
A51GPTOC*.Op.general
0
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
TRUE: 1
FALSE: 0
A51GPTOC*.Str
Information
Element picked up
0
1
A51GPTOC*.Str.general
0
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
TRUE: 1
FALSE: 0
Information
Element picked up and Fwd Direction
0
1
0
Element picked up and Rev Direction
1
0
0
A51GPTOC*.Str.dirGeneral
2
1
0
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
No-Dir: 0
FWD: 1
REV: 2
Information List
Input/Output Matrix
General
Pickup
User Logic
Type
IEC
60870-5-1
03
DNP3
MODBUS
RTU
Inhibit 51G-n
Inhibit 51G-n
Input
E/F off/on
Control
Y
Y
Y
51G-n
Pickup
51G-n Pickup
Output
51G-n
51G-n Operated
Output
Y
Y
Y
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.15.7
Protection and Automation Functions
5.15 51G Time-Delayed Earth Fault – Measured
254
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019