Instruments
The device instrumentation and metering provides real-time measured quantities and data, this is displayed on
the relay fascia LCD (when in
Instruments Mode
) or via the data communications interface.
The primary values are calculated using the CT and VT parameters i.e. the values entered in the
Configura-
tion > CT/VT
menu, (see
The user can add the meters that are most commonly viewed to a
Favorites
window by pressing the
Enter
key when viewing a meter. The relay will display the favorite meters after elapse of the
Configuration >
Device > Favorite Meters Timer
setting. When more than 1 favorite meter is selected each selected
meter is displayed on the LCD for 5 seconds.
The energy storage meters can be reset from a binary input and have a user selectable setting for their meas-
urement in the
Configuration > Data Storage
).
Counter instruments can be reset by pressing the ▶ key when the instrument is displayed.
Communication Meters
The communications meters display the information and activity.
The screen itself depends on the module type and is available only in English.
Control Mode Menu
This mode provides convenient access to commonly used relay control and test functions. When any of the
items highlighted in the control menu are selected control is initiated by pressing the
Enter
key. The user is
prompted to confirm the action, again by pressing the
Enter
key, before the command is executed.
i
i
NOTE
Control ID access code entry may be necessary to carry out control commands from the device, (see
i
i
NOTE
A CB must be in a
Closed
state before an
Open
command will be accepted. And that a CB must be in an
Open
state before a
Close
command will be accepted. If not, the relay reports that the requested
command is
Interlocked
.
i
i
NOTE
Switching a protection function
In/Out
via the
Control Mode
menu will not change that function
group’s
Enabled/Disabled
setting. The
Control Mode
menu selection will however over-ride the
setting when disabling or switching the function out of service.
Reading Indications using Reydisp
Instruments and meters can be accessed locally from the front USB port or remotely from the rear data comms
ports using Reydisp.
See the
Engineering Guide
for full details.
3.1.3
Device Functionality
3.1 Device Fascia
Reyrolle 7SR5, Transformer Protection Device, Device Manual
45
C53000-G7040-C015-1, Edition 11.2019