Error Messages and Trouble-Shooting
9-9
FC 56
J31069-D0155-U001-A0-7618
Table 9-2
Error messages via the “error_code” variable
Error Code
(B#16#..)
Description
H1 32
init_run cannot be executed. Cyclic process image to the ASM is faulty. FC 56 reports
timeout of the process image to the ASM.
The timeout time can be adjusted as necessary in DBB 58 of UDT 10. The default value
is 50 (dec) = 2 seconds. Greater values (max. of 255) will lengthen the timeout time.
S
ASM_address is incorrectly parameterized in UDT 10. ASM_address may be
located on a wrong module.
S
ASM_channel is parameterized
w
16 or
v
0.
S
ASM hardware/firmware is faulty.
S
The same physical ASM channel is used for two (or more) UDT 10 structures.
Check ASM_address and ASM_ channel for all UDT 10 structures.
H1 33
An init_run was not correctly concluded. The process image is not consistent.
S
Execute init_run again.
S
Turn ASM off and on again.
S
The RUN-STOP switch on the CPU was activated quickly several times (particularly
with slow PROFIBUS baud rates).
S
The same physical ASM channel is used for two (or more) UDT 10 structures.
Check ASM_address and ASM_ channel for all UDT 10 structures.
H1 34
Without waiting for the ready signal, the user started an init_run while another init_run
command was already being executed.
S
Do not set init_run cyclically.
S
The same physical ASM channel is used for two (or more) UDT 10 structures.
Check ASM_address and ASM_channel for all UDT 10 structures.
H1 35
The ASM has failed.
S
Power failure on the MOBY-ASM
S
PROFIBUS plug disconnected or PROFIBUS cable disconnected.
S
ASM_address or ASM_channel does not exist.
This error is indicated when the ASM_failure bit (see chapter 3.2) is set in OB 122.
OB 122 is called when the FC 56 is no longer able to access the cyclic word to the
MOBY ASM.
H1 36
S
The pointer to the command (Command_DB_number/Command_DB_address)
doesn’t exist on the SIMATIC.
S
Definition of Command_DB on the SIMATIC is too short. Use UDT 50 for the
definition.
H1 37
The parameterized value of MOBY_mode (UDT 10) is outside the permissible range
from 0 to F.
H1 38
The parameterized value of MDS_IO_control is outside the permissible range from
0 to 7.
H8 0A
ASM is not ready (temporary message).
S
This message is given to a user who is not using the FC 56 and is polling the ASMs
acyclically, one after the other, very quickly.
H8 22
H8 23
Area length error while reading a parameter
Area length error while writing a parameter
This error code indicates that parameter x is completely or partially outside the operand
area or the length of a bit field for an ANY parameter is not divisible by 8.
Summary of Contents for MOBY FC 56
Page 12: ...Introduction 1 6 FC 56 J31069 D0155 U001 A0 7618 ...
Page 63: ...5 1 FC 56 J31069 D0155 U001 A0 7618 Sample Applications 5 ...
Page 80: ...Sample Applications 5 18 FC 56 J31069 D0155 U001 A0 7618 ...
Page 90: ...Entry Exit Check of an MDS in an SLG Field 6 10 FC 56 J31069 D0155 U001 A0 7618 ...
Page 94: ...System Configuration 7 4 FC 56 J31069 D0155 U001 A0 7618 ...
Page 100: ...Commissioning Guidelines 8 6 FC 56 J31069 D0155 U001 A0 7618 ...
Page 101: ...9 1 FC 56 J31069 D0155 U001 A0 7618 Error Messages and Trouble Shooting 9 ...
Page 152: ...Programming MOBY ASM on PROFIBUS DP V1 B 30 FC 56 J31069 D0155 U001 A0 7618 ...