Error Messages and Trouble-Shooting
9-4
FC 56
J31069-D0155-U001-A0-7618
Table 9-2
Error messages via the “error_code” variable
Error Code
(B#16#..)
Description
B0 02
MDS_IO_control 1:
S
A command has been issued, but there is no MDS in the transmission window of the
SLG.
S
The dialog battery of the MDS 507 is dead. (It is not mandatory to set the LR_bat bit.
Measure battery voltage.)
MDS_IO_control 0:
S
The old/current MDS has moved out of the transmission window and the next/new
MDS has entered the transmission window. A command has been issued (not
NEXT). This command refers to the new MDS, but the old/current MDS has not
been terminated with NEXT.
S
A new MDS entered the transmission window of the SLG and left it again without
any command being processed (MDS has “slipped through”).
B0 08
Antenna not on or SET-ANT = ON with antenna already turned on
S
User error. Adhere to command sequence.
B0 09
Buffer overflow on MOBY driver of the ASM/SLG. Internal system error.
S
Perform init_run of the ASM.
B0 10
Driver error. Communication between filehandler and MDS driver has malfunctioned
(AB byte).
S
Perform init_run of the ASM.
B0 11
Communication error between filehandler and MDS driver. The MDS driver reported a
RESET termination although the filehandler did not process a RESET.
S
Perform init_run of the ASM.
B0 12
Unmotivated startup message of MDS driver on the ASM
S
Perform init_run of the ASM.
C0 02
Memory error message from MDS. The MDS has not yet been written or has lost its
memory contents due to battery failure (not with EEPROM MDS).
S
Replace the MDS or battery (if the battery_low is set).
S
Initialize the MDS with the STG 4F.
S
Format the MDS using the FORMAT command.
C0 06
During certain important operations (e.g. writing system area of MDS, formatting MDS)
the MDS must not leave the transmission window of the SLG, as otherwise the
command will terminate with this error. Therefore:
S
Issue the command again
S
MDS is situated on the edge of the SLG transmission window
C0 07
S
The FORMAT or TRACE commands have been issued with incorrect parameters.
The physical address requested does not exist in the MDS (MDS memory is smaller
than specified in the command)
S
With READ/WRITE/UPDATE: the pointer in the FAT is incorrect; it is pointing to a
block that does not exist in the MDS.
Summary of Contents for MOBY FC 56
Page 12: ...Introduction 1 6 FC 56 J31069 D0155 U001 A0 7618 ...
Page 63: ...5 1 FC 56 J31069 D0155 U001 A0 7618 Sample Applications 5 ...
Page 80: ...Sample Applications 5 18 FC 56 J31069 D0155 U001 A0 7618 ...
Page 90: ...Entry Exit Check of an MDS in an SLG Field 6 10 FC 56 J31069 D0155 U001 A0 7618 ...
Page 94: ...System Configuration 7 4 FC 56 J31069 D0155 U001 A0 7618 ...
Page 100: ...Commissioning Guidelines 8 6 FC 56 J31069 D0155 U001 A0 7618 ...
Page 101: ...9 1 FC 56 J31069 D0155 U001 A0 7618 Error Messages and Trouble Shooting 9 ...
Page 152: ...Programming MOBY ASM on PROFIBUS DP V1 B 30 FC 56 J31069 D0155 U001 A0 7618 ...