Error Messages and Trouble-Shooting
9-10
FC 56
J31069-D0155-U001-A0-7618
Table 9-2
Error messages via the “error_code” variable
Error Code
(B#16#..)
Description
H8 24
H8 25
Area length error while reading a parameter
Area length error while writing a parameter
This error code indicates that parameter x is located in an area which is not allowed for
the system function.
H8 26
The parameter contains a time location number which is too large.
H8 27
The parameter contains a counter location number which is too large.
H8 28
H8 29
Offset error while reading a parameter
Offset error while writing a parameter
The reference to parameter x is an operand whose bit address is not 0.
H8 30
H8 31
The parameter is located in the write-protected global DB.
The parameter is located in the write-protected instance DB.
H8 32
H8 34
H8 35
The parameter contains a DB number which is too large.
The parameter contains an FC number which is too large.
The parameter contains an FB number which is too large.
H8 3A
H8 3C
H8 3E
The parameter contains the number of a DB which is not loaded.
The parameter contains the number of an FC which is not loaded.
The parameter contains the number of an FB which is not loaded.
H8 42
H8 43
An access error occurred while the system was trying to read a parameter from the I/O
area of the inputs.
An access error occurred while the system was trying to write a parameter to the I/O
area of the outputs.
H8 44
H8 45
Error during the nth (n > 1) read attempt after occurrence of an error
Error during the nth (n > 1) write attempt after occurrence of an error
H8 7F
Internal error in parameter x. Cannot be corrected by the user.
H8 90
Specified logical base address is invalid: No assignment in SDB1/SDB2x exists, or it is
not a base address.
H8 92
A type other than BYTE has been specified in an ANY reference.
H8 93
The area identifier contained in the configuration (SDB1, SDB2x) of the logical address
is not permitted for these SFCs. Permitted:
S
0 = S7-400
S
1 = S7-300
S
2, 7 = DP modules
H8 A0
Negative acknowledgment while reading from module. FC fetches acknowledgment
although no acknowledgment is ready.
A user who is not using the FC 56 would like to fetch DR 101 (or DR 102 to 104)
although no acknowledgment is available.
S
Perform an init_run for new synchronization between ASM and application.
H8 A1
Negative acknowledgment while writing to the module. FC sends command although
ASM is unable to receive a command.
H8 A2
DP protocol error in layer 2. Could be a hardware defect.
H8 A3
DP protocol error in Direct-Data-Link-Mapper or User-Interface/User. Could be a hard-
ware defect.
Summary of Contents for MOBY FC 56
Page 12: ...Introduction 1 6 FC 56 J31069 D0155 U001 A0 7618 ...
Page 63: ...5 1 FC 56 J31069 D0155 U001 A0 7618 Sample Applications 5 ...
Page 80: ...Sample Applications 5 18 FC 56 J31069 D0155 U001 A0 7618 ...
Page 90: ...Entry Exit Check of an MDS in an SLG Field 6 10 FC 56 J31069 D0155 U001 A0 7618 ...
Page 94: ...System Configuration 7 4 FC 56 J31069 D0155 U001 A0 7618 ...
Page 100: ...Commissioning Guidelines 8 6 FC 56 J31069 D0155 U001 A0 7618 ...
Page 101: ...9 1 FC 56 J31069 D0155 U001 A0 7618 Error Messages and Trouble Shooting 9 ...
Page 152: ...Programming MOBY ASM on PROFIBUS DP V1 B 30 FC 56 J31069 D0155 U001 A0 7618 ...