Error Messages and Trouble-Shooting
9-11
FC 56
J31069-D0155-U001-A0-7618
Table 9-2
Error messages via the “error_code” variable
Error Code
(B#16#..)
Description
H8 B0
S
SFC not possible for module type
S
Data record unknown to module
S
Data record number
w
241 is not allowed.
S
Data records 0 and 1 are not permitted for SFC 58 “WR_REC.”
H8 B1
The length specified in the RECORD parameter is wrong.
H8 B2
The configured slot is not occupied.
H8 B3
Actual module type is not the module type specified in SDB1.
H8 C0
S
RDREC:
The module has record, but it doesn’t have any read data.
S
WRREC:
ASM is not ready to accept new data.
→
Wait until the cyclic counter is incremented.
H8 C1
The data of the preceding write job on the module for the same data record have not yet
been processed by the module.
H8 C2
The module is currently processing the maximum possible number of jobs for a CPU.
H8 C3
Required resources (memory, etc.) are currently in use.
This error is not reported by the FC 56. If this error occurs, the FC 56 waits until the
system is able to provide resources again.
H8 C4
Communication error
S
Parity error
S
SW ready not set
S
Error in block length management
S
Checksum error on CPU side
S
Checksum error on module side
H8 C5
Distributed I/O not available
Kx xx
QUEUE WRITE parameter incorrect (DAT_DB_number/DAT_DB_address or length)
Option 0000 Hex:
The file entry with number xxx or xxx + 1 specified in DAT_DB_number is incorrect. The
method of counting the file entries in DAT_DB_number begins with 1.
Option 0001 Hex:
The file entry with number xxx or xxx + 1 specified in DAT_DB_number contains a file
name that already exists on the MDS. The method of counting the file entries in
DAT_DB_number begins with 1.
Note:
The data entries are counted in decimal format.
Summary of Contents for MOBY FC 56
Page 12: ...Introduction 1 6 FC 56 J31069 D0155 U001 A0 7618 ...
Page 63: ...5 1 FC 56 J31069 D0155 U001 A0 7618 Sample Applications 5 ...
Page 80: ...Sample Applications 5 18 FC 56 J31069 D0155 U001 A0 7618 ...
Page 90: ...Entry Exit Check of an MDS in an SLG Field 6 10 FC 56 J31069 D0155 U001 A0 7618 ...
Page 94: ...System Configuration 7 4 FC 56 J31069 D0155 U001 A0 7618 ...
Page 100: ...Commissioning Guidelines 8 6 FC 56 J31069 D0155 U001 A0 7618 ...
Page 101: ...9 1 FC 56 J31069 D0155 U001 A0 7618 Error Messages and Trouble Shooting 9 ...
Page 152: ...Programming MOBY ASM on PROFIBUS DP V1 B 30 FC 56 J31069 D0155 U001 A0 7618 ...