Appendix C:
Tr
oubleshoot
ing
To display Echo Confidence in the RUN mode
Press
and hold for four seconds (Failsafe Time Left changes to the Short:Long
Confidence display).
To display Echo Confidence in the program mode, access the Echo Confidence (P805)
parameter.
To update the value displayed after each aiming adjustment..
Press
(five times or more to verify stability and overcome any echo lock P711).
Increase Failsafe Timer Value
Increase the Failsafe Timer (P070) value, if failsafe operation will not be compromised by
the larger value.
Try this only if LOE shows for short periods of time.
Install a Transducer with a Narrower Beam
Sometimes the interference echoes from the sides of a vessel can cause the MultiRanger
to lock onto a consistent, incorrect level. Try installing a longer range (narrower beam)
transducer, enter the new transducer model (P004), and (if necessary) optimize aiming
and frequency again.
Always contact your Siemens Milltronics service personnel before selecting a transducer
to solve this type of problem.
Use Dolphin Plus to Debug Echo
If a narrower beam transducer is not available, use Dolphin Plus to view live sonic
profiles and make adjustments to the Advanced Echo Processing parameters.
Fixed Reading
If the Reading is a fixed value, regardless of the transducer to material surface distance,
ensure the:
1.
Transducer acoustic beam is free from obstruction.
2.
Transducer is properly aimed
3.
Transducer is not in contact with any metal object.
4.
Material mixer (if used) is operating while the MultiRanger is operating. If it is
stopped, ensure that the mixer blade is not stopped under the transducer.
Obstructions in the Sound Beam
Check for (and remove if present) any acoustic beam obstruction, or relocate the
transducer.
If an obstruction cannot be removed or avoided, adjust the Time Varying Threshold (TVT)
Curve to reduce the Echo Confidence derived from the sound reflected by the obstruction.
Use Dolphin Plus to adjust the TVT curve. (See
P832: TVT Shaper.
)
Nozzle Mountings
If the transducer is mounted on or in a nozzle, grind smooth any burrs or welds on the
inside or open end (the end that opens into the vessel). If the problem persists, install a
Summary of Contents for MAG 1100
Page 1: ... MFDUSPNBHOFUJD GMPXNFUFST 1 8 0QFSBUJOH OTUSVDUJPOT p 4 53 4 ...
Page 47: ......
Page 76: ... MFDUSPNBHOFUJD GMPXNFUFST 1 8 0QFSBUJOH OTUSVDUJPOT p 4 53 4 ...
Page 140: ...65 SITRANS F M 8 Commissioning 8 3 2 MAG 5000 CT and MAG 6000 CT Menu overview ...
Page 164: ...Tab 36 Siemens MultiRanger 100 ...
Page 165: ...Instruction Manual April 2006 100 200 multiranger ...
Page 396: ...Page 222 MultiRanger 100 200 INSTRUCTION MANUAL 7ML19981FB05 mmmmm Parameters ...
Page 445: ...Operation Manual February 2005 ECHOMAX xrs 5 ...
Page 446: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM ...
Page 454: ...Page EN 8 XRS 5 Series Transducers OPERATION MANUAL 7ML19985QT81 mmmmm English ...
Page 462: ...Side DA 8 XRS 5 Serie Transducere DRIFTSVEJLEDNING 7ML19985QT81 mmmmm Dansk ...
Page 470: ...Seite 8 Ultraschallsensoren XRS 5 BETRIEBSANLEITUNG 7ML19981QT81 mmmmm Deutsch ...
Page 478: ...Σελίδα EL 8 Μορφοτροπείς σειράς XRS 5 ΕΓΧΕΙΡΙ ΙΟ ΛΕΙΤΟΥΡΓΙΑΣ 7ML19985QT81 mmmmm Ελληνικά ...
Page 486: ...Página ES 8 Sensores XRS 5 MANUAL DE OPERACIÓN 7ML19985QT81 mmmmm Español ...
Page 494: ...Page FR 8 Transducteurs Série XRS 5 MANUEL D UTILISATION 7ML19985QT81 mmmmm Français ...
Page 502: ...Pagina IT 8 Trasduttori serie XRS 5 MANUALE OPERATIVO 7ML19985QT81 mmmmm Italiano ...
Page 510: ...Pagina NE 8 XRS 5 serie transducers BEDIENINGSHANDLEIDING 7ML19985QT81 mmmmm Nederlands ...
Page 518: ...Página PT 8 Transdutores Série XRS 5 MANUAL DE FUNCIONAMENTO 7ML19985QT81 mmmmm Português ...
Page 526: ...sivu SU 8 XRS 5 sarjan anturit KÄYTTÖOPAS 7ML19985QT81 mmmmm Suomi ...
Page 534: ...Sida SV 8 XRS 5 Transducerserier ANVÄNDARMANUAL 7ML19985QT81 mmmmm Svenska ...
Page 539: ...Operation Manual February 2005 ECHOMAX xps xct ...
Page 540: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM ...
Page 550: ...Page EN 10 XPS XCT Series Transducers OPERATION MANUAL 7ML19985QM82 English ...
Page 555: ...Tab 37 Siemens XRS 5 Ultrasonic Level Sensors ...
Page 556: ...Operation Manual February 2005 ECHOMAX xrs 5 ...
Page 557: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM ...
Page 565: ...Page EN 8 XRS 5 Series Transducers OPERATION MANUAL 7ML19985QT81 mmmmm English ...
Page 573: ...Side DA 8 XRS 5 Serie Transducere DRIFTSVEJLEDNING 7ML19985QT81 mmmmm Dansk ...
Page 581: ...Seite 8 Ultraschallsensoren XRS 5 BETRIEBSANLEITUNG 7ML19981QT81 mmmmm Deutsch ...
Page 589: ...Σελίδα EL 8 Μορφοτροπείς σειράς XRS 5 ΕΓΧΕΙΡΙ ΙΟ ΛΕΙΤΟΥΡΓΙΑΣ 7ML19985QT81 mmmmm Ελληνικά ...
Page 597: ...Página ES 8 Sensores XRS 5 MANUAL DE OPERACIÓN 7ML19985QT81 mmmmm Español ...
Page 605: ...Page FR 8 Transducteurs Série XRS 5 MANUEL D UTILISATION 7ML19985QT81 mmmmm Français ...
Page 613: ...Pagina IT 8 Trasduttori serie XRS 5 MANUALE OPERATIVO 7ML19985QT81 mmmmm Italiano ...
Page 621: ...Pagina NE 8 XRS 5 serie transducers BEDIENINGSHANDLEIDING 7ML19985QT81 mmmmm Nederlands ...
Page 629: ...Página PT 8 Transdutores Série XRS 5 MANUAL DE FUNCIONAMENTO 7ML19985QT81 mmmmm Português ...
Page 637: ...sivu SU 8 XRS 5 sarjan anturit KÄYTTÖOPAS 7ML19985QT81 mmmmm Suomi ...
Page 645: ...Sida SV 8 XRS 5 Transducerserier ANVÄNDARMANUAL 7ML19985QT81 mmmmm Svenska ...
Page 650: ...Tab 38 Siemens XPS XCT Transducers ...
Page 651: ...Operation Manual February 2005 ECHOMAX xps xct ...
Page 652: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM ...
Page 662: ...Page EN 10 XPS XCT Series Transducers OPERATION MANUAL 7ML19985QM82 English ...