9.2
Connection diagram
A1
10V GND E1
D1
11
14
D
C
O
u
t
An
a
lo
g
I
n
D
ig
it
a
l
In
GR25V-6IK.BD.1R / GR31M-6ID.BD.2R
EMUN19K1
29.04.2015
K1
max. AC 250 V 2 A
Signal
0...10 V
+
Signal PWM
f = 1...10 kHz
7
6
5
2
10 kΩ
10 kΩ
1
0
V
G
N
D
E1
E1
G
N
D
15...28 V
+
-
L1
N
PE
Netzspannung
Leistungsschild
Line voltage
Rating-plate
1
A
(D+)
B
(D-)
MO
D
BU
S
(R
S-4
8
5
)
3
1
0
V
E1
4
1
Line voltage
rating plate
2
Relay output for fault indication (contact rating max. AC 250 V 2 A)
3
MODBUS (RS-485) interface
4
Factory-installed bridge between 10 V and E1 for 100 % speed
5
Input for speed setting by 0...10 V signal / potentiometer (R
i
> 100 k
Ω
)
6
Voltage supply 10 V DC (I
max
50 mA)
7
Speed setting by PWM signal (f = 1...10 kHz)
Assembly instructions
ECblue
Enclosure
L-BAL-F065-GB 1617 Index 004
Part.-No. 00702801-GB
25/28