Chapter 8
Operating Instructions
ICR845-2 Image Code Reader
116
©
SICK AG · Division Auto Ident · Germany · All rights reserved
8012377/ 0000/ 2008-01-30
Troubleshooting
Malfunctions when reading 1D codes (bar codes)
Fault
Possible cause
Remedy
1. No Read
The "Result" LED
(default setting: "Good Read") does not
light up at the end of the reading pulse.
– The "Result 2" switching output (de-
fault setting: "Good Read") does
not output a pulse
– the ICR845-2 outputs the status
ST = 2 in the reading result of the
host interface (if ST is enabled for out-
put in the Reading data on the
D
ATA
S
TRINGS
tab; this is not selected
in the default setting)
– the ICR845-2 outputs the system
message "no code" via the auxiliary in-
terface (Terminal Emulator of CLV-
Setup)
Read not successful, since there was no
bar code in the illumination field during
the reading pulse
Bar code type not activated for reading
Code not completely within the distance-
dependent field of view
Configured resolution lower than
required
Configured number of multiple reads not
reached
The bar code is tilted excessively with
respect to the illumination field
The reading angles at which the bar code
appears to the ICR845-2 are too large
Evaluation criteria for bar code not
set correctly
First perform the reading while the code
is stationary, then while the code is
moved. Check the content of the image
memory with CLV-Setup/ImageFTP: trig-
ger the ICR845-2; is the code in the im-
age memory once the reading cycle is
complete??
All bar code types are deactivated in the
default setting. With CLV-Setup:
Select the C
ODE
C
ONFIGURATION
tab and
find the 1D S
YMBOLOGIES
section.
Click the checkbox of the desired code
type. Click the relevant E
DIT
button.
Make the settings on the tab of the se-
lected code type. Download to the
ICR845-2!
Check with image output via ImageFTP:
Has all the code been recorded in the im-
age memory? Is the code too long?
With CLV-Setups:
Select the R
EADING
C
ONFIGURATION
tab and
enter the correct value for "Minimum bar
width 1D" in the R
EADING PARAMETERS
sec-
tion. Download to the ICR845-2.
Extend the reading pulse, reduce the
number with CLV-Setup
With CLV-Setup:
Select the C
ODE
C
ONFIGURATION
tab and
find the 1D D
ECODER
section.
Select the SMART decoder.
Download to the ICR845-2.
With CLV-Setup:
Select the C
ODE
C
ONFIGURATION
tab and
find the 1D D
ECODER
section.
Select the Standard decoder.
Download temporarily to the ICR845-2.
Start P
ERCENTAGE
E
VALUATION
.
Observe the reading quality (reading
quality > 70 %!). Realign ICR845-2 if
necessary. If ok, choose SMART decod-
er. Download to the ICR845-2.
With CLV-Setup:
Select the C
ODE
C
ONFIGURATION
tab and
find the 1D S
YMBOLOGIES
section.
Enable all code types (except Pharma-
code), set code lengths to
FREE
.
Download temporarily to the ICR845-2.
Start P
ERCENTAGE
E
VALUATION
.
Tab. 8-7: Troubleshooting: Result-status output errors in Reading mode (reading bar codes)