- 44 -
Setting items in the Pattern setting group are shown below.
Character,
Factory Default
Setting Item, Function, Setting Range
Setting pattern number
• Selects the setting pattern number.
• Selection item:
0 to 15
Step 0 step SV
• Sets Step 0 step SV.
Step SV is the value at the end of the step.
• Setting range:
SV low limit to SV high limit
Step 0 step time
• Sets Step 0 step time.
Step time is the processing time of the step.
• Setting range:
, 0:00 to 99:59
Time unit follows the selection in [Step time unit].
If the
key is pressed at 0:00,
will be set.
When
is set, Fixed value control will be performed using step SV at
Step 0.
Step 0 PID block number
• Selects PID block number used for Step 0.
• Selection item:
0 to 9
Step 0 Time signal 1 block number
• Selects Time signal 1 block number used for Step 0.
Selects any one number from a maximum of 16 Time signal blocks.
The same number can be selected as many times as desired.
• Selection item:
0 to 15
Available when Time signal output (TS option) is ordered, and when Time signal
output TS1 is selected in [Time signal output TS1/Status (RUN) output].
Step 0 Time signal 2 block number
• Selects Time signal 2 block number used for Step 0.
Selects any one number from a maximum of 16 Time signal blocks.
The same number can be selected as many times as desired.
• Selection item:
0 to 15
Available when Time signal output (TS option) is ordered, and when Time signal
output TS2 is selected in [Time signal output TS2/Status (HOLD) output].
Step 0 Time signal 3 block number
• Selects Time signal 3 block number used for Step 0.
Selects any one number from a maximum of 16 Time signal blocks.
The same number can be selected as many times as desired.
• Selection item:
0 to 15
Available when Time signal output (TS option) is ordered, and when Time signal
output TS3 is selected in [Time signal output TS3/Status (WAIT) output].