- 54 -
7.2.4 Alarm Block Setting Group
In Alarm block setting group, the following can be set for blocks 0 to 9:
EV1 alarm value, EV2 alarm value, EV3 alarm value, EV4 alarm value
•
Alarm output
EV1 alarm output actions are shown below.
The same applies to EV2 alarm output, EV3 alarm output and EV4 alarm output.
• High limit alarm
• High limit with standby alarm
Alarm output is in standby.
(Fig. 7.2.4-1)
(Fig. 7.2.4-2)
• Low limit alarm
• Low limit with standby alarm
Alarm output is in standby.
(Fig. 7.2.4-3)
(Fig. 7.2.4-4)
• High/Low limits alarm
• High/Low limits with standby alarm
Alarm output is in standby.
(Fig. 7.2.4-5)
(Fig. 7.2.4-6)
ON
EV1 hysteresis
OFF
SV
+EV1 value
-EV1 value
ON
EV1 hysteresis
OFF
-EV1 value
SV
+EV1 value
ON
EV1 hysteresis
OFF
SV
-EV1 value
+EV1 value
ON
EV1 hysteresis
OFF
SV
-EV1 value
+EV1 value
ON
EV1 hysteresis
OFF
SV
EV1 value
EV1 value
ON
EV1 hysteresis
OFF
EV1 value
SV
EV1 value