12.14 Event Output Parameter Setting Group
Upper left: PTN Display, PV Display
The PTN Display is unlit, and the PV Display indicates setting item characters.
Lower left: STEP Display, SV/MV/TIME Display
The STEP Display is unlit, and the SV/MV/TIME Display indicates factory default value.
Right side: Indicates the setting item and setting range.
Character,
Factory Default
Setting Item, Setting Range
Data
Event output EV1 allocation
[Event Output Allocation Table]
Selection
Event output
Remarks
No event
Alarm output, High limit alarm
Alarm output, High limit with
standby alarm
Alarm output, Low limit alarm
Alarm output, Low limit with
standby alarm
Alarm output, High/Low limits alarm
Alarm output, High/Low limits
with standby alarm
Alarm output, High/Low limit range
alarm
Alarm output, High/Low limit range
with standby alarm
Alarm output, Process high alarm
Alarm output, Process high
with standby alarm
Alarm output, Process low alarm
Alarm output, Process low
with standby alarm
Pattern end output
Loop break alarm output
Output during AT
Turns ON during AT.
When
001 to 012 (Alarm output) is selected, one alarm can be set to one event
output. When 013 to 015 is selected, each output is common to multiple event
outputs.
EV1 alarm hysteresis
Thermocouple, RTD input: 0.1 to 1000.0
( )
DC voltage, current input: 1 to 10000
(The placement of the decimal point
follows the selection.)
Available when 001 to 012 (Alarm output) is selected in [Event output EV1
allocation].
EV1 alarm delay time
0 to 10000 sec
Available when 001 to 012 (Alarm output) is selected in [Event output EV1
allocation].
EV1 alarm Energized/De-energized
: Energized
: De-energized
Available when 001 to 012 (Alarm output) is selected in [Event output EV1
allocation].