- 67 -
Character,
Factory Default
Setting Item, Function, Setting Range
: Pt100 -148.0 to 212.0
: Pt100 -148.0 to 932.0
: 4 to 20 mA DC -2000 to 10000
: 0 to 20 mA DC -2000 to 10000
: 0 to 10 mV DC -2000 to 10000
: -10 to 10 mV DC -2000 to 10000
: 0 to 50 mV DC -2000 to 10000
: 0 to 100 mV DC -2000 to 10000
: 0 to 1 V DC -2000 to 10000
: 0 to 5 V DC -2000 to 10000
: 1 to 5 V DC -2000 to 10000
: 0 to 10 V DC -2000 to 10000
Scaling high limit
• Sets scaling high limit value.
• Setting range:
Scaling low limit value to Input range high limit value
Scaling low limit
• Sets scaling low limit value.
• Setting range:
Input range low limit value to Scaling high limit value
Decimal point place
• Selects decimal point place.
• Selection item:
: No decimal point
: 1 digit after decimal point
: 2 digits after decimal point
: 3 digits after decimal point
: 4 digits after decimal point
Available for DC voltage and current inputs.
Sensor correction
• Sets sensor correction value.
[Sensor correction function]
When a sensor cannot be set at the exact location where control is desired, the
sensor-measured temperature may deviate from the temperature in the
controlled location. When using multiple indicating controllers, sometimes the
measured temperatures do not concur due to differences in sensor accuracy or
dispersion of load capacities. In such a case, the control can be set at the desired
temperature by adjusting the input value of sensors. However, it is effective
within the input rated range regardless of the sensor correction value.
PV after sensor correction= Current PV + (Sensor correction value)
• Setting range:
Thermocouple, RTD input: -200.0 to 200.0
( )
DC voltage, current input: -2000 to 2000
(The placement of the decimal point
follows the selection.)