- 110 -
8.2.2 Finishing Fixed Value Control
There are 2 ways to finish Fixed value control:
Using the
key, or using External operation input
• Using the
key
Press the
key for approximately 1 second during Fixed value control.
Fixed value control will stop, and the unit will revert to Program control Stop (in Standby).
• Using External operation input
Close terminals
23
(STOP) and
27
(COM) of External operation input.
Fixed value control will stop, and the unit will revert to Program control Stop (in Standby).
(Fig. 8.2.2-1)
Fixed value control RUN
Fixed value control is finished.
Within 0.1 sec
0.1 sec min.
(STOP) and
(COM)
Closed (ON)
(STOP) and
(COM)
Open (OFF)
Controller action
Fixed value control is finished by detecting signal edge action
from OFF to ON of terminals
(STOP) and
(COM).