- 56 -
Setting items in the Alarm block setting group are shown below.
When 001 to 012 (Alarm output) is selected in [Event output EV
allocation], the following will appear.
Character,
Factory Default
Setting Item, Function, Setting Range
Block 0 EV1 alarm value
• Sets Block 0 EV1 alarm value.
• Setting range:
Type
Setting Range
No alarm action
High limit alarm
– (Input span) to Input span
(*1)
(Alarm action is disabled when set to 0 or 0.0.)
High limit with
standby alarm
– (Input span) to Input span
(*1)
(Alarm action is disabled when set to 0 or 0.0.)
Low limit alarm
– (Input span) to Input span
(*1)
(Alarm action is disabled when set to 0 or 0.0.)
Low limit with
standby alarm
– (Input span) to Input span
(*1)
(Alarm action is disabled when set to 0 or 0.0.)
High/Low limits
alarm
0 to Input span
(*1)
(Alarm action is disabled when set to 0 or 0.0.)
High/Low limits
with standby alarm
0 to Input span
(*1)
(Alarm action is disabled when set to 0 or 0.0.)
High/Low limit
range alarm
0 to Input span
(*1)
(Alarm action is disabled when set to 0 or 0.0.)
High/Low limit
range with standby
0 to Input span
(*1)
(Alarm action is disabled when set to 0 or 0.0.)
Process high alarm Input range low limit to Input range high limit
(*2)
Process high with
standby alarm
Input range low limit to Input range high limit
(*2)
Process low alarm
Input range low limit to Input range high limit
(*2)
Process low with
standby alarm
Input range low limit to Input range high limit
(*2)
(*1)
For DC voltage, current input, the input span is the same as the scaling span.
(*2)
For DC voltage, current input, input range low (or high) limit value is the same as scaling low (or
high) limit value.
Available when 001 to 012 (Alarm output) is selected in [Event output EV1 allocation],
Block 0 EV2 alarm value
• Sets Block 0 EV2 alarm value.
• Setting range:
Same as that of Block 0 EV1 alarm value.
Available when 001 to 012 (Alarm output) is selected in [Event output EV2 allocation].
Block 0 EV3 alarm value
• Sets Block 0 EV3 alarm value.
• Setting range:
Same as that of Block 0 EV1 alarm value.
Available when 001 to 012 (Alarm output) is selected in [Event output EV3 allocation].