8.3.1 Switching to Manual Control
To switch to Manual control, select “
(Manual)” in [Auto/Manual control switch], and press
the
key.
When control action is switched to manual, the MAN and MV indicators light up, the STEP Display
indicates
, and the SV/MV/TIME Display indicates the MV.
To increase or decrease the MV, use the
or
key.
Pressing the
or
key and
keys at the same time, makes MV change faster.
MV setting range:
When control action is switched to Manual during Program control Stop (in Standby):
[Output block 0 OUT1 low limit] to [Output block 0 OUT1 high limit]
If D
option is ordered: – [Output block 0 OUT2 high limit] to [Output block 0 OUT1 high limit]
[D
option (DR, DS, DA option): Heating/Cooling control output OUT2]
When control action is switched to Manual during program control:
[OUT1 low limit of running step output block number] to
[OUT1 high limit of running step output block number]
If D
option is ordered: – [OUT2 high limit of running step output block number] to
[OUT1 high limit of running step output block number]
[D
option (DR, DS, DA option): Heating/Cooling control output OUT2]
Performs Manual control using the increased/decreased MV.
Power ON
Basic Procedure
RUN mode
RUN mode [Program control Stop (in Standby)]
Pattern setting group
Auto/Manual control switch group
(5 times)
Setting Details
Power ON
Auto/Manual control
switch group
Auto/Manual control switch
Manual control
Auto/Manual control switch
Manual control
Manual control
The MAN and MV indicators light, and
the STEP Display indicates
.
or
Manual control
(e.g.) 30.0%