7.4 AT Perform Group
In AT Perform group, the following can be set:
AT mode, AT Perform/Cancel, AT bias
•
To enter AT Perform group
Press the
key once in RUN mode, and press the
key 3 times. The PV Display indicates
,, and the unit enters the AT Perform group.
Press the
in the AT Perform group. The PV Display indicates
, and the unit enters ‘AT
mode’.
•
Explanation of Setting Item
Upper left: PTN Display, PV Display
The PTN Display is unlit, and the PV Display indicates setting item characters.
Lower left: STEP Display, SV/MV/TIME Display
The STEP Display is unlit, and the SV/MV/TIME Display indicates factory default.
Right side: Indicates the setting item, explanation of its function, and setting range.
AT mode
• Selects AT mode.
• Selection item:
: Normal mode
Setting items in the AT Perform group are shown below.
Character,
Factory Default
Setting Item, Function, Setting Range
AT mode
• Selects AT mode.
Multi mode is enabled only during program control.
• Selection item:
: Normal mode
When AT Perform is selected in [AT Perform/Cancel], AT starts
immediately.
: Multi mode
AT is automatically performed at the point where 90% of
progressed step time has elapsed.
If there are the same PID block numbers in one pattern, the AT is
performed only for the first step.
AT Perform/Cancel
• Selects AT Perform/Cancel.
AT continues to perform when input errors (overscale, underscale) occur.
AT will be forced to stop if it has not been completed within 4 hours.
• Selection item:
: AT Cancel
: AT Perform
PTN Display
STEP Display
PV Display
SV/MV/TIME Display
Setting item, function, setting range (or selection item)