- 90 -
Character,
Factory Default
Setting Item, Function, Setting Range
Step SV Hold function when program ends
• When program control ends, selects either ‘Holding’ or ‘Not holding’ of the
Step SV Hold function.
If ‘Holding’ is selected, the PTN Display flashes when program control ends,
and control performs using the step SV of the last step.
By pressing the
key for 1 second, the Step SV Hold function is
cancelled, and the unit returns to Program control Stop (in Standby).
•
How to set program pattern when ‘Holding’ is selected
:
Set the last step values (of the program pattern in the Pattern setting group
– except step time), to all steps which have not been set yet.
Set the step time to 0:00.
• Selection item:
: Not Holding (of Step SV Hold function)
: Holding (of Step SV Hold function)
Time signal output TS1 / Status (RUN) output
• Selects either Time signal output or Status (RUN) output for Time signal
output TS1.
• Selection item:
: Time signal output TS1
: Status (RUN) output
Available when Time signal output (TS option) is ordered.
Time signal output TS2 / Status (HOLD) output
• Selects either Time signal output or Status (HOLD) output for Time signal
output TS2.
• Selection item:
: Time signal output TS2
: Status (HOLD) output
Available when Time signal output (TS option) is ordered.
Time signal output TS3 / Status (WAIT) output
• Selects either Time signal output or Status (WAIT) output for Time signal
output TS3.
• Selection item:
: Time signal output TS3
: Status (WAIT) output
Available when Time signal output (TS option) is ordered.
Time signal output TS4 / Status (FAST) output
• Selects either Time signal output or Status (FAST) output for Time signal
output TS4.
• Selection item:
: Time signal output TS4
: Status (FAST) output
Available when Time signal output (TS option) is ordered.