- 134 -
Standard Function
Wait function
During program control, the program does not proceed to the next step
until the deviation between PV and SV enters SV Wait value at the end
of step.
The STEP Display flashes while the Wait function is working.
Hold function
During program control, progress of current step can be suspended.
Pressing the
key cancels suspension, and program control
resumes.
During manual control, suspension cannot be cancelled.
Advance function
Interrupts current step during program control, and proceeds to the
beginning of the next step.
Return-to-previous function
Stops current performing step, and returns to the previous program
step. If the elapsed time of the current step is less than 1 minute, the
program control returns to the beginning of the previous step.
If the elapsed time of the current step is longer than 1 minute, the
program control returns to the beginning of the current step.
This function is disabled at Step 0 of started pattern, but returns to the
beginning of Step 0.
Repetitions and pattern link
function
Patterns 0 to 15 can be linked to the next pattern. Only pattern numbers
in numerical order can be linked. For Pattern 15, Pattern 0 can be
linked.
Number of repetitions for Patterns 0 to 15: 0 to 9999 times.
For repetitions of linked pattern, the whole linked pattern will be
repeated as many times as set in “starting pattern number”.
Step time speed-up function During program control, makes step time progress 60 times faster
while the
key is pressed.
If the Wait function is set, the Wait function has priority.
Program clearing
When program control is stopped (in Standby), and if the
key is
pressed for 3 seconds at any items in Pattern setting group, program
pattern data (for current step on the STEP Display and all the following
steps) will return to the factory default value.
Power restore action
If power fails during program control, the controller can be operated
depending on the selection in [Power restore action].
Stops after power is restored: Stops program control, and returns to
Standby mode.
Continues after power is restored: Continues (Resumes) previous
program control after power is restored.
Suspends after power is restored: Suspends (on hold) current program
control, and performs control using the step SV at the point of
suspension. Pressing the
key cancels suspension, and
program control resumes.
Progressing time error when power is restored: 1 minute
Pattern end function
If Pattern end output is selected in [Event output EV
allocation],
Pattern end output is turned ON after program control is finished, and
the SV/MV/TIME Display flashes
.
By pressing the
key for approximately 1 second, Pattern end
output is turned OFF, and the unit returns to Program control Stop (in
Standby). If Pattern end output time is set, Pattern end output is
automatically turned OFF after Pattern end output time has expired. The
unit returns to Program control Stop (in Standby).