Explanation of Mode
Mode
Description
RUN mode
The unit enters the RUN mode when power is turned ON.
Resumes from Program control Stop (in Standby) or Program control RUN,
depending on the status at power OFF.
Indication differs depending on the status below.
Program control
Stop (in Standby)
PV, SV and PTN indicators light up.
The PV Display indicates PV.
The PTN Display indicates the pattern number.
Other indicators and Displays are unlit.
Program control
RUN
PV, SV, PTN, STEP, PROFILE, Time unit and
Action indicators are lit.
The PV Display indicates PV.
The SV/MV/TIME Display indicates SV, MV or TIME.
The PTN Display indicates the pattern number.
The STEP Display indicates the step number.
Group selection mode
Selects a group from the following:
Pattern setting group, Block setting group, Repetitions and Pattern link
setting group, AT perform group, Engineering setting group,
Auto/Manual control switch group
Key Operation
Key Operation
Description
,
If any key is pressed, the unit moves to the next item, illustrated by an arrow.
Press the
key until the desired setting item appears.
Returns to RUN mode from any mode.
Moves back to the previous mode (opposite to when the
or
key is
pressed).
+
When the
and
key are pressed at the same time, the mode
returns to the previous setting group as follows.
+
Return-to-Previous Function
If
and
keys are pressed at the same time during program control
RUN, interrupts performing step, and the unit moves back to the previous
step, and performs control.
However, if the elapsed time of the current step is less than 1 minute, the
program control goes back to the beginning of the previous step. If the
elapsed time in the current step is longer than 1 minute, the program
control goes back to the beginning of the current step.
The Return-to-Previous Function is disabled at Step 0 of started pattern,
but moves back to the beginning of Step 0.
Program clearing function
When program control is stopped (in Standby), and if the
key is
pressed for approximately 3 seconds at any item in pattern setting group,
data (for current step on the STEP Display and all the following steps) will
return to the factory default.
+
+
(3 sec)
Data clearing function
When program control is stopped (in Standby), and if the
,
and
keys are pressed simultaneously for 3 seconds, the PV Display indicates
, and all program data – except Input type, OUT1 proportional cycle,
OUT2 proportional cycle – will return to the factory default. It takes approx.
30 seconds for data clear.
Block setting
group
Alarm block
setting group
EV4 alarm
value
+
+