- 109 -
(Table 8.2.1-1)
Pattern
No.
Terminal No.
*
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15
⑪
DI1
⑫
DI2
⑬
DI3
⑭
DI4
*
This pattern number is selected via the keypad.
Event Input DI1 and DI2:
Select a pattern for which step time is set to
at (2), by closing DI1 or DI2 terminal
and the COM terminal.
: Close DI1 or DI2 terminal and the COM terminal.
(e.g.) To select Pattern 3 to perform, close
⑪
&
⑮,
and close
⑫
&
⑮
respectively.
(Table 8.2.1-2)
Pattern
No.
Terminal No.
*
1
2
3
⑪
DI1
⑫
DI2
*
This pattern number is selected via the keypad.
(4) Execute Fixed Value Control
There are 2 ways to execute Fixed value control:
Using the
key, or using External operation input
• Using the
key.
Press the
key in Program control Stop (in Standby).
The step, for which step time is set to
at (2), is held, and
Fixed value control is performed using step SV.
The RUN indicator flashes during Fixed value control.
• Using External operation input
Close terminals
26
(RUN) and
27
(COM) of External operation input.
The step, for which step time is set to
at (2), is held, and
Fixed value control is performed using step SV.
The RUN indicator flashes during Fixed value control.
(Fig. 8.2.1-1)
Fixed value control RUN
Within 0.1 sec
0.1 sec min.
(RUN) and
(COM)
Closed (ON)
(RUN) and
(COM)
Open (OFF)
Controller action
Fixed value control performs by detecting signal edge action
from OFF to ON of terminals
(RUN) and
(COM).