11
Technical data and dimension sheets
Technical data
Operating Instructions – MOVIMOT
®
flexible
374
11.3.4
Current carrying capacity of terminals
Current carrying capacity of terminals
Line terminals
X1
24 A (max. loop-through current)
Control terminals
X9
10 A (max. loop-through current)
11.3.5
DC 24 V supply
Input for the independent backup voltage supply of the electronics
DC 24 V input
24V_IN
U
IN
= DC 24 V -10%/+20% according to EN 61131-2
Current consumption:
I
E
≤ 500 mA, typically 250 mA for electronics
•
Plus up to 100 mA for the safety option
•
Plus up to 100 mA for 2 digital outputs (50 mA each)
•
Plus up to 500 mA, for sensor supply
0V24_IN
11.3.6
DC 24 V auxiliary output
Internal voltage supply, only for non-safety-related enable signal via STO input
DC 24 V auxiliary out-
put
X9
24V_OUT
U
OUT
= DC 24 V -10%/+20% according to EN 61131-2
External-voltage-proof and short-circuit proof
Permitted output current: I
OUT
≤ 50 mA
0V24_OUT
11.3.7
Digital inputs
Digital inputs
Number of inputs
4 (+ 2)
Input type
PLC-compatible according to EN 61131-2 (digital inputs type 3)
DI01 – DI04: R
i
≈ 4.5 kΩ, sampling cycle ≤ 2 ms
DIO01 – DIO02: R
i
≈ 4.0 kΩ, sampling cycle ≤ 2 ms
Signal level
DC +11 to +30 V
= "1" = Contact closed
DC -3 to +5 V
= "0" = Contact open
Sensor/actuator supply
DC 24 V to EN 61131-2,
External-voltage-proof and short-circuit proof
Maximum line length
30 m
Permitted total current for
internal supply
250 mA (total of all connected sensors/actuators, maximum individual load:
250 mA)
Permitted total current for
external supply
500 mA (total of all connected sensors/actuators, maximum individual load:
500 mA)
29128668/EN – 12/2019