8.7.8
Fault 10 Data Flexibility
Subfault: 10.1
Description: Initialization
Response: Application stop + output stage inhibit
Cause
Measure
Init task error.
The init task has issued a return code != 0. Check
the program.
Subfault: 10.2
Description: Illegal operation code
Response: Application stop + output stage inhibit
Cause
Measure
Illegal opcode in Data Flexibility program.
Contact SEW-EURODRIVE Service.
Subfault: 10.3
Description: Memory access
Response: Application stop + output stage inhibit
Cause
Measure
Memory area violated while accessing array.
For example, an array access results in writing
beyond the permitted memory range. Check the
program.
Subfault: 10.4
Description: Stack
Response: Application stop + output stage inhibit
Cause
Measure
Overflow of Data Flexibility stack detected.
Check the program.
Subfault: 10.5
Description: Division by 0
Response: Application stop + output stage inhibit
Cause
Measure
Division by 0.
Check the program.
Subfault: 10.6
Description: Runtime
Response: Application stop + output stage inhibit
Cause
Measure
Runtime error/watchdog.
Check the program. The program execution time
exceeds the permitted time.
PDI or PDO tasks.
Check the program. The execution time of the
PDI or PDO task exceeds the permitted time.