8
Service
Fault table standard
Operating Instructions – MOVIMOT
®
flexible
243
Subfault: 25.70
Description: Incompatible card configuration
Response: Emergency stop + output stage inhibit
Cause
Measure
The current configuration of the cards does not
match the state of the stored startup.
For example, a card was removed that was still
present during startup.
– Restore the original configuration of the cards.
– Acknowledge the fault by manual reset with
parameter set acceptance. Setting under [Diag-
nostics] > [Status] > [Fault status] parameter
"Manual fault reset".
8.6.20
Fault 26 External fault
Subfault: 26.1
Description: Terminal
Response: External fault
Cause
Measure
Error message about external error source.
Programmable via 8622.5 (default: application
stop (with output stage inhibit)).
Subfault: 26.3
Description: Power section emergency shutdown
Response: Output stage inhibit
Cause
Measure
Power section requested external emergency
shutdown because it detected critical fault.
Contact SEW‑EURODRIVE Service.
Subfault: 26.4
Description: External braking resistor fault
Response: Response to external braking resistor fault
Cause
Measure
External braking resistor's temperature switch
connected to terminal tripped.
– Check the resistor mounting position.
– Clean the resistor.
– Check the configuration of the resistor.
– Install a larger resistor.
– Check the trip switch settings.
– Optimize the travel cycle so that less regenera-
tive operation energy arises.