8
Service
Fault table CiA402 profile
Operating Instructions – MOVIMOT
®
flexible
294
Subfault: 23.6
Description: Process data timeout
Response: Emergency stop + output stage inhibit
Cause
Measure
Power section communication interface detected
process data timeout.
If the error occurs repeatedly, contact
SEW‑EURODRIVE Service.
Subfault: 23.7
Description: Parameter communication timeout
Response: Emergency stop + output stage inhibit
Cause
Measure
Power section communication interface detected
timeout in parameter communication.
If the error occurs repeatedly, contact
SEW‑EURODRIVE Service.
Subfault: 23.8
Description: Parameter communication error
Response: Emergency stop + output stage inhibit
Cause
Measure
Power section communication interface detected
error in parameter communication.
If the error occurs repeatedly, contact
SEW‑EURODRIVE Service.
Subfault: 23.9
Description: Firmware of power section corrupt
Response: Output stage inhibit
Cause
Measure
Failed to update firmware on power section.
Update the firmware again.
8.7.19
Fault 25 Parameter memory monitoring
Subfault: 25.2
Description: NV memory – runtime error
Response: Emergency stop + output stage inhibit
Cause
Measure
Runtime error of non-volatile memory system.
– Reset the device.
If this error occurs repeatedly, replace device.
Contact SEW-EURODRIVE Service.