8
Service
Fault table CiA402 profile
Operating Instructions – MOVIMOT
®
flexible
311
Subfault: 33.15
Description: Firmware configuration
Response: Output stage inhibit
System state: Fault acknowledgment with CPU reset
Cause
Measure
The Device Update Manager detected a modified
version of the application firmware.
Acknowledge the error. Doing so will update the
configuration data of the Device Update Manager.
The error occurs repeatedly several times. The
Device Update Manager is outdated and cannot
save the configuration.
Update the Device Update Manager.
8.7.27
Fault 34 Process data configuration
Subfault: 34.1
Description: Changed process data configuration
Response: Application stop + output stage inhibit
Cause
Measure
Process data configuration changed during active
process data operation.
– Stop the process data and make your changes.
Then start the process data again.
– Perform a reset. Doing so will stop the process
data, apply the changes, and restart the process
data.
8.7.28
Fault 35 Function activation
Subfault: 35.1
Description: Activation key – application level invalid
Response: Emergency stop + output stage inhibit
Cause
Measure
The activation key was entered incorrectly.
Enter the activation key again.
The activation key was not created for this
device.
Check the activation key.
When using a double axis, the activation key for
the wrong instance was entered in the device.
Enter the activation key for the allocated instance.
An activation key for a technology level was
entered in the parameter "Application level – Ac-
tivation key".
Enter the activation key in the correct parameter.
29128668/EN – 12/2019