8
Service
Fault table standard
Operating Instructions – MOVIMOT
®
flexible
238
Subfault: 23.4
Description: Hardware fault
Response: Output stage inhibit
Cause
Measure
A fault occurred in a hardware component of the
power section, e.g.: Overcurrent hardware com-
parator.
– Check the current supply.
– Increase the ramp time.
– Check for correct motor size (the motor current
is too high).
– Contact SEW-EURODRIVE Service.
Switched-mode power supply fault, hardware
fault.
– Check the current supply.
– Check the DC 24 V supply voltage.
Fault at the gate driver of an IGBT.
Defect in the power output stage. Contact
SEW‑EURODRIVE Service.
Invalid process data configuration. Status of con-
trol section and power section are not compatible.
Contact SEW-EURODRIVE Service.
Subfault: 23.5
Description: Invalid process data configuration
Response: Output stage inhibit
Cause
Measure
Invalid process data configuration.
Contact SEW-EURODRIVE Service.
Subfault: 23.6
Description: Process data timeout
Response: Emergency stop + output stage inhibit
Cause
Measure
Power section communication interface detected
process data timeout.
If the error occurs repeatedly, contact
SEW‑EURODRIVE Service.
Subfault: 23.7
Description: Parameter communication timeout
Response: Emergency stop + output stage inhibit
Cause
Measure
Power section communication interface detected
timeout in parameter communication.
If the error occurs repeatedly, contact
SEW‑EURODRIVE Service.
Subfault: 23.8
Description: Parameter communication error
Response: Emergency stop + output stage inhibit
Cause
Measure
Power section communication interface detected
error in parameter communication.
If the error occurs repeatedly, contact
SEW‑EURODRIVE Service.
29128668/EN – 12/2019