8
Service
Fault table CiA402 profile
Operating Instructions – MOVIMOT
®
flexible
319
Subfault: 52.2
Description: Impermissible system function
Response: Output stage inhibit
Cause
Measure
Impermissible system function activated.
Disable impermissible functions when Ex protec-
tion function is active, such as "Activate standstill
current" = "On" in the active control mode.
Subfault: 52.3
Description: Inverter too large
Response: Output stage inhibit
Cause
Measure
Ratio of inverter current to nominal motor current
too large.
Check the assignment of motor and inverter, and
check the dimensioning of the system.
Subfault: 52.4
Description: Parameterization of current limit characteristic
Response: Output stage inhibit
Cause
Measure
Error while setting parameters for current limit
characteristic.
– Parameterize the current limit characteristic.
– Perform startup again.
Subfault: 52.5
Description: Time duration exceeded f < 5 Hz
Response: Emergency stop + output stage inhibit
Cause
Measure
Duration of 60 s for f < 5 Hz exceeded.
Check the dimensioning of the system: If speed
control = FCB05, increase the speed. If
speed = 0, inhibit output stage / with stop FCBs,
activate the brake function if a brake is installed.
29128668/EN – 12/2019