5
Electrical installation
Assignment of the optional plug connectors
Operating Instructions – MOVIMOT
®
flexible
128
Connection of cables with open end
The following table shows the conductor assignment of cables with the following part
numbers:
Part numbers
28127587, 28127560, 28127579, 28127552
Assembly
Open cable end
Description
Prefabricated plug
connectors
PE
U
A
B
W
V
Core
color/
Core
cross sec-
tion
Identi-
fication
Assembly
Signal
Contact
Brown
2.5 mm
2
4.0 mm
2
L1
Not pre-
fabricated
Line connection, phase L1
L1
U
Black
2.5 mm
2
4.0 mm
2
L2
Not pre-
fabricated
Line connection, phase L2
L2
V
Grey
2.5 mm
2
4.0 mm
2
L3
Not pre-
fabricated
Line connection, phase L3
L3
W
Green/yel-
low
2.5 mm
2
4.0 mm
2
–
Not pre-
fabricated
PE connection
PE
PE
Brown
2.5 mm
2
–
Not pre-
fabricated
DC 24 V input
+24V
A
Blue
2.5 mm
2
–
Not pre-
fabricated
0V24 reference potential
0V24
B
White
0.34 mm
2
–
Not pre-
fabricated
Reserved
1)
Res.
–
Yellow
0.34 mm
2
–
Not pre-
fabricated
Reserved
1)
Res.
–
Blue
0.34 mm
2
–
Not pre-
fabricated
Reserved
1)
Res.
–
Orange
0.34 mm
2
–
Not pre-
fabricated
Reserved
1)
Res.
–
1) Reserved wires must be isolated and fixed in the connection box.
29128668/EN – 12/2019