8
Service
Fault table CiA402 profile
Operating Instructions – MOVIMOT
®
flexible
286
Subfault: 16.40
Description: Data of selected motor not valid
Response: Output stage inhibit
Cause
Measure
Startup data set on replaceable memory module
not valid for this motor.
Replace the memory module.
Subfault: 16.41
Description: Data of selected motor do not exist
Response: Output stage inhibit
Cause
Measure
No startup data set found on the replaceable
memory module for the selected motor.
Check the selection and, if necessary, start up
another motor or replace the memory module.
8.7.13
Fault 17 Internal processor fault
Subfault: 17.7
Description: Exception error
Response: Output stage inhibit
Cause
Measure
Exception trap in CPU.
Contact SEW-EURODRIVE Service.
8.7.14
Fault 18 Software errors
Subfault: 18.1
Description: Motor management
Response: Output stage inhibit
System state: Fault acknowledgment with CPU reset
Cause
Measure
Error detected at motor management interface.
– Switch the device off and on again.
– Contact SEW‑EURODRIVE Service if the error
persists.
Subfault: 18.3
Description: Task system warning
Response: Warning
Cause
Measure
Error while processing internal task system. This
may be a timeout for cyclical tasks, for example.
– Acknowledge the warning.
– Contact SEW-EURODRIVE Service if the warn-
ing occurs regularly.
29128668/EN – 12/2019